Circuit separator transformer with double insulation, built according to UNE-EN-61558-2 -15 – Directive 2014/35 / EU.
Class HC windings (200º) and Class B insulation (120º). Ta = 40ºC.
Windings impregnated in varnish. Tropicalized.
Voltage test: PRI / SEC: 4.5 kV – PRI / MAS: 4.5 kV – SEC / MAS: 4.5 kV.
Double insulation with electrostatic screen (P) between windings, connected to earth terminal.
Protection against electric shock class I.
Max leakage current with respect to earth <5mA.
Io <3% * In.
Low induction – Voltage drop between vacuum and load less than 5%.
PTC thermal sensors of 110ºC connected to voltage-free terminals.
Degree of protection of the IP-00 enclosure, according to UNE 20324-EN 60529.
Connection group Ii. Secondary with midpoint (PM)
Frequency 50-60 Hz.
Possibility of vertical or horizontal mounting.
Lifting bolts from 5 KVA.